Contact Information: 1-800-991-7026 | 1-919-372-8413 | sales@automationindustrial.com
FREE DOMESTIC GROUND SHIPPING! (see shipping policies below for more details)
ALL ORDERS SHIP SAME DAY! (if placed before 3PM EST)
- Product Number: F4-04DA-1
- Made By: Facts Engineering
- Part Series: DirectLogic 405
- Model Type: Analog Current Output Module
- Channels: 4
- Range: 4-20mA Only
- Resolution: 12 bit
- Minimum External Load Resistance: 0Ω
- Conversion Time (Settling): 100µs Max
- Conversion Time (Digital-Analog Out): 2.0ms Max
- External Power Supply: 24VDC
- Power Consumption: 70mA
-
Are the outputs source or sink on the F4-04DA-1?
- The F4-04DA-1 uses sink-type outputs.
-
What is the peak output voltage supported by the F4-04DA-1?
- If clamped and transient suppressed, the F4-04DA-1 can handle peak voltage of up to 40VDC.
-
Can the F4-04DA-1 be used to replace a F4-04DA?
- Yes, this model was intended to act as a direct replacement for this older variant.
⭐⭐⭐⭐ 4.0
The F4-04DA-1 is highly accurate, reliable, and easy to use. The smaller number of channels and fixed output range can limit its versatility somewhat, but it is otherwise a remarkably high-quality DL405 current output module. -Automation Industrial Quality Assurance Manager
Description
|
General Information about the Product |
|
|
Part Number |
F4-04DA-1 f4 |
|
Description |
F4-04DA-1 by Facts Engineering Analog Output Module DL405 DirectLOGIC 405 |
|
Condition |
Pre-Owned Cleaned and Tested. With 1 Year Warranty. |
Technical Specifications | |
| Product Number | F4-04DA-1 |
| Made By | Facts Engineering |
| Part Series | DirectLogic 405 |
| Model Type | Analog Current Output Module |
| Channels | 4 |
| Range | 4-20mA Only |
| Resolution | 12 bit |
| Minimum External Load Resistance | 0Ω |
| Conversion Time (Settling) | 100µs Max |
| Conversion Time (Digital-Analog Out) | 2.0ms Max |
| External Power Supply | 24VDC |
| Power Consumption | 70mA |
Frequently Asked Questions | |
| Are the outputs source or sink on the F4-04DA-1? The F4-04DA-1 uses sink-type outputs. | |
| What is the peak output voltage supported by the F4-04DA-1? If clamped and transient suppressed, the F4-04DA-1 can handle peak voltage of up to 40VDC. | |
| Can the F4-04DA-1 be used to replace a F4-04DA? Yes, this model was intended to act as a direct replacement for this older variant. | |
Internal Review | |
|
⭐⭐⭐⭐
4.0
The F4-04DA-1 is highly accurate, reliable, and easy to use. The smaller number of channels and fixed output range can limit its versatility somewhat, but it is otherwise a remarkably high-quality DL405 current output module. -Automation Industrial Quality Assurance Manager |
|
Policies and Procedures
Shipping |
We offer FREE DOMESTIC GROUND SHIPPING on all orders unless otherwise specified. In addition to FREE DOMESTIC GROUND SHIPPING we offer UPS Next Day Air Early AM, UPS Next Day Air, UPS 2nd Day Air, and UPS 3-day Select (when applicable). Please contact us at (919) 372-8413 prior to purchase if you would like urgent shipping via any of the above expedited options. |
Returns |
All products ordered from Automation Industrial will come with our 1 YEAR WARRANTY. Any item(s) found to be defective through normal use and wear within 1 Year from the date of receipt are covered under warranty. |
Contact Us |
Contact us at 919-372-8413 or kindly submit a message via the website submission form. We look forward to hearing from you! |
Payment & Security
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
You may also like
Recently viewed
- Opens in a new window.